Gland Size vs Entry Thread
When specifying a gland there are two important factors:-
- The gland size required to fit the cable you are using
- The entry thread required to fit the equipment into which you are fitting the gland.
Below is a table showing you the gland sizes and the entry threads available. If what you require is not listed below, a gland size 20s with a 3"NPT entry thread, for example, it still may be possible to achieve your requirements by using an adaptor/reducer.
| Gland Size |
Standard ISO Thread |
Alternative Threads Generally
Available From Stock |
Special Alternative Threads Made
To Order (Subject To Economical Manufacturing Qty) |
| NPT |
ISO |
ET |
PG |
BSPP/BSPT
NPT |
| 16 |
M16 x 1.5 M20 x 1.5 |
½" or ¾" |
M25 x 1.5 |
- |
21 |
1" |
| 20S |
M20 x 1.5 |
½" or ¾" |
M25 x 1.5 |
½" |
21 |
1" |
| 20 |
M20 x 1.5 |
½" or ¾" |
M25 x 1.5 |
¾" |
29 |
1" |
| 25 |
M25 x 1.5 |
¾" or 1" |
M32 x 1.5 |
1" |
29 - 36 |
1¼" |
| 32 |
M32 x 1.5 |
1" or 1¼" |
M40 x 1.5 |
1¼" |
36 - 42 |
1½" |
| 40 |
M40 x 1.5 |
1¼" or 1½" |
M50 x 1.5 |
1½" |
42 - 48 |
2" |
| 50S |
M50 x 1.5 |
1½" or 2" |
M63 x 1.5 |
2" |
48 |
2½" |
| 50 |
M50 x 1.5 |
2" |
M63 x 1.5 |
2" |
48 |
2½" |
| 63S |
M63 x 1.5 |
2" or 2½" |
M75 x 1.5 |
2½" |
- |
3" |
| 63 |
M63 x 1.5 |
2½" |
M75 x 1.5 |
2½" |
- |
3" |
| 75S |
M75 x 1.5 |
2½" or 3" |
M80 x 2 |
3" |
- |
3½" |
| 75 |
M75 x 1.5 |
3" |
M80 x 2 |
3" |
- |
3½" |
| 80 |
M80 x 2 |
3" or 3½" |
M85 x 2
M90 x 2 |
- |
- |
4" |
| 80H |
M80 x 2 |
3" or 3½" |
M85 x 2
M90 x 2 |
- |
- |
4" |
| 85 |
M85 x 2 |
3" or 3½" |
M90 x 2 |
- |
- |
4" |
| 90 |
M90 x 2 |
3½" or 4" |
M100 x 2 |
- |
- |
- |
| 90H |
M90 x 2 |
3½" or 4" |
M100 x 2 |
- |
- |
- |
| 100 |
M100 x 2 |
3½" or 4" |
- |
- |
- |
- |
Notes:-
- Special Alternative Threads are made to order and are subject to economical manufacturing quantities.
- Peppers offers all its glands (except BW) with alternative entry threads.
- Type BWL glands with alternative entry threads are subject to economical manufacturing quantities.